TCB Metal Works, Racine, Wisconsin · tcbmetalworks.com/handrail-guardrail-code-guide/ · November 23, 2026
Railing rules come from more than one book, and they do not all say the same thing. A handrail that is right for a house can be too low for a store. A guard that passes on a factory mezzanine would fail in a school. This guide puts the numbers for Wisconsin side by side, with the code section next to each one so you can look it up yourself.
We build railings, so this is written the way we use it in the shop: what the rule is, where it is written, and what it means for the steel.
Which Code Applies
Start with what the building is and who uses it.
| The job | The rule book | Where it is written |
|---|---|---|
| Stores, offices, schools, apartments and other commercial or public buildings | Wisconsin Commercial Building Code, which adopts the 2021 International Building Code (IBC) with Wisconsin changes | SPS 361.05(1) adopts the IBC 2021. Wisconsin changes are in chapter SPS 362. |
| One- and two-family homes | Wisconsin Uniform Dwelling Code (UDC) | SPS 321.04, Stairways and elevated areas |
| Places where employees work: plants, warehouses, platforms, mezzanines | OSHA general industry rules | 29 CFR 1910.28 and 1910.29 |
| Stairs and ramps that must be accessible | 2010 ADA Standards for Accessible Design | Section 505, Handrails |
A job can fall under more than one. A factory stair is built under the building code and is also a workplace under OSHA. A ramp at a store entrance answers to the building code and to the ADA. See When More Than One Applies.
Wisconsin makes only two changes to the IBC sections covered here. It rewrites where a guard is required (SPS 362.1015, quoted below), and it adds that handrails are not required for stairs into vehicle service pits (SPS 362.1011(2)). The handrail section, IBC 1014, and the load section, IBC 1607.9, are adopted as written.
Handrail or Guard?
The codes treat these as two different things, and a railing often has to be both.
- A handrail is the rail you hold on a stair or ramp. Its rules are about the hand: height, size, and room for your fingers.
- A guard keeps people from going off an open edge. Its rules are about the fall: height, the size of the openings, and strength.
Most people say “guardrail” for a guard. OSHA uses its own words: a guardrail system on a level edge and a stair rail system along the open side of a stair.
On an open commercial stair you usually need both: a guard at 42 inches, with a handrail lower down at 34 to 38 inches.
The Numbers at a Glance
Each number carries its section. “Not stated” means the text we read gives no number for it. The details and exceptions follow in the sections below.
| Commercial buildings IBC 2021, as Wisconsin adopts it | Homes Wisconsin UDC | Workplaces OSHA general industry | Accessible routes 2010 ADA Standards | |
|---|---|---|---|---|
| Handrail height | 34 to 38 in above the tread nosingsIBC 1014.2 | 30 to 38 in above the tread nosingsSPS 321.04(3)(b)1.a. | 30 to 38 in from the leading edge of the tread1910.29(f)(1)(i) | 34 to 38 in above nosings and ramp surfacesADA 505.4 |
| Guard height | 42 in minimumIBC 1015.3 | 36 in minimum above the floorSPS 321.04(3)(c)2. | 42 in, plus or minus 3 in. Stair rails put in on or after January 17, 2017: 42 in minimum1910.29(b)(1), (f)(1)(ii)(B) | Not covered by section 505 |
| Guard needed when the drop is | More than 30 inSPS 362.1015 | More than 24 inSPS 321.04(3)(c)1.a. | 4 ft or more1910.28(b)(1)(i) | Not covered |
| Largest opening in a guard | A 4 in ball must not pass, up to 36 in high. From 36 to 42 in: 4 3/8 in ballIBC 1015.4 | A 4 3/8 in ball must not pass, pushed with 4 lbSPS 321.04(3)(c)3. | Balusters no more than 19 in apart, or a midrail halfway up1910.29(b)(2) | Not covered |
| Triangle at the stair (tread, riser, bottom rail) | A 6 in ball must not passIBC 1015.4 exc. 2 | A 6 in ball must not pass, pushed with 4 lbSPS 321.04(3)(a)3.b. | Not stated | Not covered |
| Round handrail size | 1 1/4 to 2 in outside diameterIBC 1014.3.1 | 2 in maximum diameterSPS 321.04(3)(b)5.a. | A shape and size the hand can grasp firmly1910.29(f)(5) | 1 1/4 to 2 in outside diameterADA 505.7.1 |
| Clear space, handrail to wall | 1 1/2 in minimumIBC 1014.7 | 1 1/2 in minimumSPS 321.04(3)(b)2. | 2 1/4 in minimum to any other object1910.29(f)(2) | 1 1/2 in minimumADA 505.5 |
| Handrail extensions | 12 in level past the top riser; one tread depth, still sloping, past the bottom riserIBC 1014.6 | Not stated | Not stated | 12 in level at the top; one tread depth at the bottomADA 505.10.2, 505.10.3 |
| Load on the top rail | 50 lb per foot, and a 200 lb point loadIBC 1607.9.1, 1607.9.1.1 | 200 lb in any directionSPS 321.04(3)(a)4.a. | 200 lb down or outward1910.29(b)(3), (f)(7) | Not covered |
| Load on pickets and infill | 50 lb point loadIBC 1607.9.1.2 | 50 lb on any one square footSPS 321.04(3)(a)4.b. | 150 lb on midrails and other intermediate members1910.29(b)(5) | Not covered |
Handrails in Commercial Buildings
These are the IBC 2021 rules as Wisconsin adopts them.
Where a handrail is required
- Stairs: a handrail on each side of every flight. IBC 1011.11 Stairs inside a dwelling unit and spiral stairs may have one on one side only.
- Ramps: handrails on both sides of any ramp that rises more than 6 inches. IBC 1012.8
- Wide stairs: intermediate handrails, so that every part of the required stair width is within 30 inches of a handrail. IBC 1014.9
Height
34 to 38 inches, measured straight up from the tread nosings or from the ramp surface, and the same height all the way along. IBC 1014.2 Fittings and bends that carry the rail from one flight to the next may run higher than 38 inches.
Size and shape of the grip
- Round: 1 1/4 to 2 inches outside diameter. IBC 1014.3.1
- Not round: 4 to 6 1/4 inches around, no more than 2 1/4 inches across at the widest and no less than 1 inch across at the narrowest. IBC 1014.3.1
- Edges: a radius of at least 0.01 inch, so no sharp corners. IBC 1014.3.1
What that means for common stock:
| Stock | Outside size | As a commercial handrail grip |
|---|---|---|
| 1 in pipe | 1.315 in | Fits: inside 1 1/4 to 2 in |
| 1 1/4 in pipe | 1.660 in | Fits: inside 1 1/4 to 2 in |
| 1 1/2 in pipe | 1.900 in | Fits: inside 1 1/4 to 2 in |
| 2 in pipe | 2.375 in | Too big: over 2 in |
| 1 1/2 in square tube | 6 in around, or a little less with rounded corners | Fits: perimeter inside 4 to 6 1/4 in |
| 2 in square tube | 8 in around | Too big: perimeter over 6 1/4 in |
Pipe is named by a nominal size, not its real outside diameter, which is why “1 1/2 inch pipe” is the usual commercial handrail and “2 inch pipe” does not pass.
Room for the hand
- Clear space to the wall: at least 1 1/2 inches between the handrail and a wall or other surface. IBC 1014.7
- Brackets: the gripping surface must be continuous. A bracket fixed to the bottom of the rail does not count as an obstruction as long as it does not stick out sideways past the rail within 1 1/2 inches below the bottom of the rail. IBC 1014.4
- No spinning: a handrail must not rotate in its fittings. IBC 1014.5
- Projection: a handrail may stick into the required stair or ramp width no more than 4 1/2 inches on each side. IBC 1014.8
Ends and extensions
A handrail returns to a wall, a guard or the walking surface, or it runs on into the handrail of the next flight. Where it does not run on: IBC 1014.6
- Top of a stair: it extends level at least 12 inches past the top riser.
- Bottom of a stair: it keeps sloping for the depth of one tread past the bottom riser.
- Ramps: it extends level at least 12 inches past the top and the bottom of the ramp run.
The extensions run in the same direction as the stair or ramp. Inside a dwelling unit that is not required to be accessible, the handrail only needs to run from the top riser to the bottom riser.
Guards in Commercial Buildings
Where a guard is required
Wisconsin replaces the IBC sentence with its own. A guard goes along the open side of walking surfaces, balconies, mezzanines, stairs, ramps, landings, roofs and similar surfaces meant to be used by occupants or the public, where the surface is more than 30 inches above the floor or roof below, or more than 30 inches above the grade below measured at any point within 36 inches out from the open edge. SPS 362.1015
The IBC exceptions still apply. Among them: the loading side of a loading dock, the audience side of a stage, and vehicle service pits the public cannot get to. IBC 1015.2
Height
At least 42 inches, measured straight up from the walking surface, from the line of the tread nosings on a stair, or from the ramp surface. IBC 1015.3 The exceptions a fabricator runs into most:
- Inside dwelling units in buildings of three stories or less (Group R-3, and individual units in Group R-2 with separate exits): 36 inches minimum. On the open side of their stairs, 34 inches minimum from the nosing line.
- Factory stairs (Group F) that serve fewer than three stories and are not open to the public: where the top of the guard is also the handrail, it may be 34 to 38 inches above the nosing line.
Openings
From the walking surface up to 36 inches, a 4 inch ball must not pass through any opening. From 36 to 42 inches the limit is a 4 3/8 inch ball. IBC 1015.4
- The triangle formed by the riser, the tread and the bottom rail at the open side of a stair: a 6 inch ball must not pass.
- Areas not open to the public in Group I-3, F, H and S buildings (jails, factories, hazardous and storage occupancies): the limit is a 21 inch ball.
- Walkways for reaching equipment (electrical, mechanical or plumbing): the limit is a 21 inch ball.
- Stairs inside dwelling units in Group R-2 and R-3: the limit is a 4 3/8 inch ball.
To lay out pickets that hold a gap, use our free picket spacing calculator.
Roofs and equipment
A guard is required where equipment that needs service, or a roof hatch, sits within 10 feet of a roof edge or open side that is more than 30 inches above what is below. The guard runs at least 30 inches past each end of the equipment or hatch and must stop a 21 inch ball. It is not required where fall arrest anchors that meet ANSI/ASSE Z359.1 are installed. IBC 1015.6, 1015.7
Glass
Glass used as a guard or handrail has its own rules in IBC section 2407, which this guide does not cover. IBC 1015.2.1
Loads a Railing Must Take
Under the IBC, handrails and guards are designed for each of these: IBC 1607.9
- A line load of 50 pounds per linear foot. IBC 1607.9.1 In Group I-3, F, H and S buildings, in areas the public cannot get to with an occupant load under 50, it is 20 pounds per foot. For one- and two-family dwellings only the 200 pound load below applies.
- A concentrated load of 200 pounds. IBC 1607.9.1.1
- Pickets, panels and infill, and every rail except the handrail and the top rail: a concentrated load of 50 pounds. IBC 1607.9.1.2
The IBC points to ASCE 7 sections 4.5.1, 4.5.1.1 and 4.5.1.2 for how those loads are applied. Those loads set the post size, the post spacing and, most of all, the anchorage. This page gives the loads only. Sizing the railing and its anchors to carry them is engineering work for the job at hand.
Homes: Wisconsin Uniform Dwelling Code
One- and two-family homes in Wisconsin follow SPS 321.04, not the IBC. The numbers are different.
Handrails
- When: a flight with more than 3 risers needs at least one handrail for the full length of the flight. SPS 321.04(3)(a)1.
- Height: 30 to 38 inches above the nosing of the treads, measured from the hard surface under any finish to the top of the rail. SPS 321.04(3)(b)1.a.
- Clear space to the wall: at least 1 1/2 inches. SPS 321.04(3)(b)2.
- Projection: no more than 4 1/2 inches into the required stair width on each side. SPS 321.04(3)(b)4.
- Round grip: 2 inches maximum diameter. SPS 321.04(3)(b)5.a.
- Rectangular grip: 6 1/4 inches maximum around, 2 7/8 inches maximum across. SPS 321.04(3)(b)5.b.
- Continuous for the whole stair, except that it may stop at an intermediate landing and may have newel posts. SPS 321.04(3)(b)6.
Guards
- When: on the open sides of stairs with more than 3 risers, and on the open sides of landings, platforms, balconies and porches more than 24 inches above the floor or grade. SPS 321.04(3)(a)2., (c)1.a. Outdoors, the 24 inches is measured from the lowest point within 3 feet of the edge. SPS 321.04(3)(c)1.c.
- Height: at least 36 inches above the floor, or up to the underside of a stair handrail that meets the handrail rules. SPS 321.04(3)(c)2. The code notes that a handrail at 30 to 38 inches above the nosing meets the guard height on a stair.
- Openings: a 4 3/8 inch ball must not pass when pushed with 4 pounds. In the triangle at the tread, riser and bottom rail, a 6 inch ball. SPS 321.04(3)(a)3.
- Cable and rope infill: openings no more than 3 1/2 inches, with vertical supports no more than 4 feet apart. SPS 321.04(3)(a)3.c.
- Strength: 200 pounds in any direction on handrails and guards; 50 pounds on any one square foot of infill, balusters and panels. SPS 321.04(3)(a)4.
- Outdoors: metal, decay-resistant or pressure-treated wood, or protected from the weather. SPS 321.04(3)(a)5.
For risers and treads under the same code, see our free stair calculator.
Workplaces: OSHA
OSHA’s general industry rules cover places where employees work. They are written for the employer, and they apply on top of the building code. Construction sites have their own rules in 29 CFR 1926, which this guide does not cover.
Guardrail systems on level edges
- When: an unprotected side or edge 4 feet or more above a lower level needs a guardrail, a safety net or personal fall protection. 1910.28(b)(1)(i)
- Top rail height: 42 inches, plus or minus 3 inches, above the walking surface. 1910.29(b)(1)
- In between: a midrail halfway up, or balusters no more than 19 inches apart, or mesh or panels with no opening over 19 inches wide. 1910.29(b)(2)
- Top rail strength: 200 pounds, down or outward, applied within 2 inches of the top edge. Under that load pushing down, the top rail must not drop below 39 inches. 1910.29(b)(3), (b)(4)
- Midrails, mesh and balusters: 150 pounds, down or outward. 1910.29(b)(5)
- Rail size: top rails and midrails at least 1/4 inch in diameter or thickness. 1910.29(b)(9)
Handrails and stair rails
- Handrail height: 30 to 38 inches, from the leading edge of the tread to the top of the handrail. 1910.29(f)(1)(i)
- Stair rail height: at least 42 inches if installed on or after January 17, 2017; at least 30 inches if installed before. 1910.29(f)(1)(ii)
- One rail doing both jobs: the top rail of a stair rail may serve as the handrail only when it is 36 to 38 inches high. 1910.29(f)(1)(iii)
- Finger clearance: at least 2 1/4 inches between a handrail and any other object. 1910.29(f)(2)
- Openings in a stair rail: none over 19 inches at its least dimension. 1910.29(f)(4)
- Strength: 200 pounds, down or outward, within 2 inches of the top edge. 1910.29(f)(7)
How many rails a stair needs
Every flight with at least 3 treads and at least 4 risers needs handrails and stair rails as follows:
| Stair width | Enclosed | One open side | Two open sides |
|---|---|---|---|
| Less than 44 in | At least one handrail | One stair rail system with handrail on the open side | One stair rail system on each open side |
| 44 to 88 in | One handrail on each enclosed side | One stair rail system with handrail on the open side, and one handrail on the enclosed side | One stair rail system with handrail on each open side |
| More than 88 in | One handrail on each enclosed side, and one intermediate handrail in the middle of the stair | One stair rail system with handrail on the open side, one handrail on the enclosed side, and one intermediate handrail in the middle | One stair rail system with handrail on each open side, and one intermediate handrail in the middle |
A stair landing 4 feet or more above a lower level needs a guardrail or stair rail on its open sides. 1910.28(b)(11)(i)
Accessibility: ADA Handrails
Section 505 of the 2010 ADA Standards covers handrails on accessible stairs and ramps. Most of it matches the IBC. These are the points to watch:
- Both sides of stairs and ramps. ADA 505.2
- Continuous for the full length of each flight or ramp run. Inside rails on switchback stairs and ramps are continuous between flights. ADA 505.3
- Height: 34 to 38 inches to the top of the gripping surface, held at a consistent height. ADA 505.4
- Clearance: 1 1/2 inches minimum to the adjacent surface. ADA 505.5
- Brackets: the top and sides of the grip are not obstructed, and the bottom is not obstructed for more than 20 percent of its length. Anything that sticks out sideways sits at least 1 1/2 inches below the bottom of the grip. ADA 505.6
- Cross section: round, 1 1/4 to 2 inches outside diameter; not round, 4 to 6 1/4 inches around and 2 1/4 inches maximum across. ADA 505.7
- Surfaces: rounded edges, nothing sharp or abrasive. Handrails do not rotate in their fittings. ADA 505.8, 505.9
- Extensions: 12 inches level at the top of a stair, starting directly above the first riser nosing; at the bottom, sloping for at least one tread depth past the last riser nosing; 12 inches level at the top and bottom of a ramp. Extensions return to a wall, guard or the landing. ADA 505.10
The 20 percent rule is the one that changes fabrication. A rail welded along the top of a flat bar or a solid panel has its bottom blocked the whole way, so it is not an ADA handrail. Rails carried on spaced brackets are.
When More Than One Applies
Where two rule books cover the same railing, it has to meet both. The numbers overlap enough that one railing usually can.
- Handrail height: 34 to 38 inches is inside every range on this page: IBC, UDC, OSHA and ADA.
- Clear space behind a handrail: 2 1/4 inches meets OSHA and is more than the 1 1/2 inches the IBC, UDC and ADA ask for. Watch the 4 1/2 inch limit on how far the rail may stick into the stair width.
- Guard height: 42 inches meets the IBC and falls inside OSHA’s 39 to 45 inches.
- Stair in a plant: a 42 inch stair rail with a separate handrail at 34 to 38 inches meets the IBC and OSHA numbers on this page. A single top rail doing both jobs has only a narrow window: 36 to 38 inches under OSHA, and under the IBC only on the Group F stairs described above.
- Openings: the IBC 4 inch rule is far tighter than OSHA’s 19 inches. In areas the public can reach, the IBC number is the one that sets the picket spacing.
Common Questions
How high does a handrail have to be in Wisconsin?
In commercial buildings the top of the handrail is 34 to 38 inches above the tread nosings (IBC 2021 section 1014.2, adopted by Wisconsin under SPS 361.05). In one- and two-family homes the Wisconsin Uniform Dwelling Code allows 30 to 38 inches (SPS 321.04(3)(b)1.a.).
How high does a guardrail have to be?
A guard in a commercial building is at least 42 inches high (IBC 2021 section 1015.3). In a Wisconsin home it is at least 36 inches above the floor (SPS 321.04(3)(c)2.). OSHA calls for a top rail 42 inches high, plus or minus 3 inches, in general industry workplaces (29 CFR 1910.29(b)(1)).
When is a guardrail required?
Wisconsin commercial buildings need a guard where a walking surface is more than 30 inches above the floor, roof or grade below (SPS 362.1015). Wisconsin homes need one on areas more than 24 inches above the floor or grade, and on the open sides of stairs with more than 3 risers (SPS 321.04(3)(a)2.). OSHA requires fall protection at 4 feet or more in general industry (29 CFR 1910.28(b)(1)(i)).
What is the 4 inch sphere rule?
A required guard in a commercial building may not have an opening that a 4 inch diameter ball can pass through, from the walking surface up to 36 inches. From 36 to 42 inches the limit is a 4 3/8 inch ball (IBC 2021 section 1015.4). The Wisconsin Uniform Dwelling Code uses a 4 3/8 inch ball, pushed with 4 pounds of force, for homes (SPS 321.04(3)(c)3.).
What size pipe can be used for a handrail?
A round handrail in a commercial building has an outside diameter of 1 1/4 to 2 inches (IBC 2021 section 1014.3.1; the ADA Standards section 505.7.1 give the same range). That takes in 1 inch pipe (1.315 inch outside), 1 1/4 inch pipe (1.660 inch) and 1 1/2 inch pipe (1.900 inch). 2 inch pipe is 2.375 inch outside, which is too big.
How much load does a railing have to hold?
Under IBC 2021, handrails and guards are designed for 50 pounds per linear foot and for a 200 pound concentrated load, and pickets and infill for a 50 pound concentrated load (sections 1607.9.1, 1607.9.1.1 and 1607.9.1.2). The Wisconsin Uniform Dwelling Code and OSHA both use 200 pounds on the rail.
Sources and Limits
Every number on this page was read from the code text on November 23, 2026.
- Wisconsin Administrative Code, chapters SPS 361 and 362 (Commercial Building Code) and section SPS 321.04 (Uniform Dwelling Code): the State’s own site, docs.legis.wisconsin.gov (SPS 361 to 366, SPS 321).
- International Building Code, 2021 edition, sections 1011.11, 1012.8, 1014, 1015 and 1607.9. The International Code Council publishes the official text at codes.iccsafe.org. We read these sections from published state and city adoptions of the 2021 IBC and compared three copies against each other.
- OSHA, 29 CFR 1910.28 and 1910.29: the Electronic Code of Federal Regulations (ecfr.gov) and osha.gov (1910.28, 1910.29).
- 2010 ADA Standards for Accessible Design, section 505: ada.gov.
- Pipe outside diameters: AISC Shapes Database v16.0.
What this page does not cover: glass guards (IBC 2407), assembly seating such as bleachers and stadiums (IBC 1030), construction sites (29 CFR 1926), existing buildings altered under the existing building code, and local rules. Codes are amended; if the date above is old, check the current text.
Need a railing built to these numbers? We build custom handrails and guardrails at our shop in Racine.